Avoidable thermodynamic inefficiencies evaluation of a sewage water source heat pump system

dc.contributor.authorCelik A.G.
dc.contributor.authorHepbasli A.
dc.date.accessioned2024-07-22T08:03:29Z
dc.date.available2024-07-22T08:03:29Z
dc.date.issued2023
dc.description.abstractThe performance of a sewage water source heat pump system is assessed through conventional/enhanced exergy-based methods in this present study. The experimental data used in the analyses are based the cooling mode. According to the conventional-based results, the condenser has the lowest exergy efficiency. Beside this, the enhanced exergy-based analysis results show the sewage water heat exchanger should be considered as the most significant component as it has the highest avoidable exergy destruction rate in the whole system and takes the improvement priority. Based on the enhanced exergy analysis, 56% of the total exergy destruction belongs to the avoidable part. Copyright © 2023 Inderscience Enterprises Ltd.
dc.identifier.DOI-ID10.1504/IJEX.2023.130367
dc.identifier.issn17428297
dc.identifier.urihttp://akademikarsiv.cbu.edu.tr:4000/handle/123456789/12301
dc.language.isoEnglish
dc.publisherInderscience Publishers
dc.subjectHeat pump systems
dc.subjectPumps
dc.subjectSewage
dc.subjectWaste heat
dc.subjectAdvanced exergy analyse
dc.subjectConventional exergy analyse
dc.subjectEnhanced exergy analyse
dc.subjectExergy Analysis
dc.subjectSewage water
dc.subjectSewage water source heat pump
dc.subjectSWSHP
dc.subjectWater source heat pump
dc.subjectExergy
dc.titleAvoidable thermodynamic inefficiencies evaluation of a sewage water source heat pump system
dc.typeArticle