Spectral and statistical analysis for ferroresonance phenomenon in electric power systems

dc.contributor.authorSeker, S
dc.contributor.authorAkinci, TC
dc.contributor.authorTaskin, S
dc.date.accessioned2024-07-18T12:02:43Z
dc.date.available2024-07-18T12:02:43Z
dc.description.abstractThis study presents our findings on the ferroresonance phenomenon for the Seyitomer-Isiklar part of the Electric Power System of 380 kV in Turkey. In this context, the power spectral density approach and Short-Time Fourier Transforms are applied to the voltage variations for phase R of the sample power network. The findings show that the ferroresonance event can be represented by the interharmonics between 50 and 250 Hz, as well as statistical properties. In addition, a histogram of the ferroresonance region shows a different characteristic from the overall data and the non-ferroresonance region. This different characteristic can be defined by an asymmetrical distribution characteristic, and its numerical measure is given by the Noise to Signal Ratio of 0.624.
dc.identifier.issn0948-7921
dc.identifier.other1432-0487
dc.identifier.urihttp://akademikarsiv.cbu.edu.tr:4000/handle/123456789/8632
dc.language.isoEnglish
dc.publisherSPRINGER
dc.titleSpectral and statistical analysis for ferroresonance phenomenon in electric power systems
dc.typeArticle

Files